MD‑SI‑DP1 Communication
‑183‑
8 MD-SI-DP1 Communication
8.1 Introduction
As a PROFIBUS DP fieldbus adapter card that meets international PROFIBUS fieldbus
standards, the MD‑SI‑DP1 expansion card can improve the communication efficiency
of the AC drive and implement the networking function, enabling the AC drive to be a
slave controlled by the fieldbus master. It can implement PROFIBUS DP
communication.
The following table lists the differences between MD‑SI‑DP1 and MD38DP2.
Item MD‑SI‑DP1 MD38DP2
Diagnosis
Supported Supported
DPV1
Supported Supported
PPO4
Supported Supported
PPO type
Set by the Siemens software
tool
Set by the Siemens software
tool
PZD mapping address
Set by the Siemens software
tool
Set by the Siemens software
tool
Station number settings
Set by the DIP switch,
ranging from 1 to 125
Set by the DIP switch,
ranging from 1 to 125
Master disconnection
AC drive informed by the
expansion card
AC drive informed by the
expansion card
Communication rate
between the expansion card
and the AC drive
Constant rate Constant rate
Slave fault
Master informed by the
expansion card
Master informed by the
expansion card
CAN communication
Not supported Supported
8.2 Installation
The MD‑SI‑DP1 expansion card is embedded in the MD520 series AC drive. Before
installation, cut off the power supply of the AC drive and wait for about 10 minutes
until the charging indicator of the AC drive becomes off. Then, insert the MD‑SI‑DP1
card into the AC drive and fasten the screws to prevent the signal socket between
boards from being damaged by the pulling force of the external signal cable. "
Figure
8–1
"
on page 184
shows the installation.