Modbus Communication
‑30‑
}
Definition of communication parameter addresses:
The parameters can be read and written (except those which cannot be changed
because they are only for factory use or monitoring).
3.5 Related Parameters
Table 3–5 Parameters related to Modbus communication
Pa
rame
ter
Parameter
Name
Default
Value
Value Range Description
FD‑00 RS485 baud
rate
5005 Ones: Modbus
0: 300 bit/s
1: 600 bit/s
2: 1200 bit/s
3: 2400 bit/s
4: 4800 bit/s
5: 9600 bit/s
6: 19200 bit/s
7: 38400 bit/s
8: 57600 bit/s
9: 11,5200 bit/s
Tens: Reserved
Hundreds: Reserved
Thousands: CAN baud rate
0: 20
1: 50
2: 100
3: 125
4: 250
5: 500
6: 1M
This parameter defines the rate of data transmission
between the host controller and the AC drive. A higher
baud rate indicates faster communication.
Note that the baud rate of the host controller must be the
same as that of the AC drive. Otherwise, communication
will fail.
FD‑01 RS485 data
format
0 0: No check (8‑N‑2)
1: Even parity check (8‑E‑
1)
2: Odd parity check (8‑O‑
1)
3: No check (8‑N‑1)
4: No check (7‑N‑2)
5: Even parity check (7‑E‑
1)
6: Odd parity check (7‑O‑
1)
7: No check (7‑N‑1) (valid
for Modbus)
Note that the data format set in the host controller must
be the same as that set in the AC drive. Otherwise,
communication will fail.