EtherNet/IP Communication
‑233‑
I/O Message Data Returned by the AC Drive
I/O Messages 0
AC drive running state, which is described
as follows by bit:
Bit0: 0: Stopped; 1: Running
Bit1: 0: Running in forward direction; 1:
Running in reverse direction
Bit2: 0: Not faulty; 1: Faulty
Bit3: 0: Running frequency not reached; 1:
Running frequency reached Bit4 to Bit7:
Reserved
Bit8 to bit15: AC drive fault code
I/O Messages 1
AC drive running frequency (unit: 0.01 Hz)
The current AC drive running frequency is
returned as 16‑bit signed data.
I/O Messages 2 to I/O Messages 11
Function parameter values (group F and
group A) and monitoring parameter values
(group U) read in real time. FE‑22 to FE‑31
correspond to I/O Messages 2 to I/O
Messages 11. For details about the
configuration, see the I/O message data
configuration.
9.6 Related Parameters
9.6.1 AC Drive Communication Card Type Setting
After powering on the AC drive, the MD500‑EN1 card can communicate with the AC
drive properly only after F0‑28 is set to 1.