PROFIBUS DP Communication
154
AC Drive Response Data PZD
PZD3 to PZD12
Function parameter values (group F and group A) and monitoring
parameter values (group U) read in real time
FE‑22 to FE‑31 correspond to PZD3 to PZD12. For the configuration, see
PZD data configuration.
After communication with the PLC is established, FE‑02 to FE‑11 display
the parameter values written into PZD3 to PZD12. Manual settings of
parameters in group FE of the AC drive are invalid.
7.6 Related Parameters
7.6.1 AC Drive Communication Card Type Setting
After powering on the AC drive, the MD38DP2 card can communicate with the AC
drive properly only after F0‑28 is set to 1.
Parameter Parameter
Name
Value Range
Setpoint Description
F0‑28
Serial
communication
protocol
0: Modbus
protocol
1:
Communication
card network
bridge protocol
1
Serial
communication
protocol
as the serial
communication
protocol.
F0‑02
Command
source
0: Operating
panel
1: Terminal
2:
Communication
2
Set the
command
source to
communication.
F0‑03
Main frequency
reference source
0: Digital setting
(non‑retentive
at power failure)
1: Digital setting
(retentive at
power failure)
2: AI1
3: AI2
4: AI3
5: Pulse
reference (DI5)
6: Multi‑
reference
7: Simple PLC
8: PID
9:
Communication
9
Set the target
frequency
through
communication.