CANopen & CANlink Communication
52
4.3 Related Parameters
Table 4–10 Related parameters
Parameter Parameter
Name
Default Value Value Range
Description
FD‑00
Baud rate
5005
Ones: Modbus
0: 300 bit/s
1: 600 bit/s
2: 1200 bit/s
3: 2400 bit/s
4: 4800 bit/s
5: 9600 bit/s
6: 19200 bit/s
7: 38400 bit/s
8: 57600 bit/s
9: 11,5200 bit/s
Tens: Reserved
Hundreds:
Reserved
Thousands: CAN
baud rate
0: 20
1: 50
2: 100
3: 125
4: 250
5: 500
6: 1M
This parameter
defines the rate
of data
transmission
between the
host controller
and the AC
drive. A higher
baud rate
indicates faster
communication.
Note that the
baud rate of the
host controller
must be the
same as that of
the AC drive.
Otherwise,
communication
will fail.
FD‑02
Local address
1 1 to 247
The uniqueness
of the local
address (except
the broadcast
address) is the
prerequisite for
point‑to‑point
communication
between the
host controller
and AC drive.
In the same
network, all
station numbers
must be unique.
Otherwise,
communication
will fail.