EasyManua.ls Logo

Inovance MD520 Series - Page 195

Inovance MD520 Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MD‑SI‑DP1 Communication
194
Parameter
Parameter
Name
Value Range Setpoint Description
F0‑28
Serial
communication
protocol
0: Modbus protocol
1: Communication
card network
bridge protocol
1
Select the special
communication card
network bridge as the
serial communication
protocol.
Communication Control Parameters
Parameter Parameter
Name
Value Range Hexadecimal
Address
Decimal Address
U3‑16 Frequency
reference
Maximum
frequency to
+Maximum
frequency
Unit: 0.01 Hz
H7310 29456
U3‑17
Control
command
0001: Run in
forward direction
0002: Run in
reverse direction
0003: Jog in
forward direction
0004: Jog in
reverse direction
0005: Coast to stop
0006: Decelerate to
stop
0007: Reset upon
fault
H7311 29457
U3‑18
DO control
Bit0: DO1 output
control
Bit1: DO2 output
control
Bit2: Relay 1
output control
Bit3: Relay 2
output control
Bit4: FMR output
control
Bit5: VDO1
Bit6: VDO2
Bit7: VDO3
Bit8: VDO4
Bit9: VDO5
H7312 29458
U3‑19
AO1 control
0 to 7FFF,
indicating 0% to
100%
H7313 29459

Table of Contents