Modbus Communication
‑27‑
Similarly, multi‑write can be performed on up to 12 consecutive parameters at a time.
If a slave detects a communication frame error or reading/writing failure caused by
other reasons, it returns an error frame.
Note
No response is returned for CRC check error.
The slave read response error command is 0x83, the write response error command is
0x86, and the multi‑write response error command is 0x90.