User manual of EC160 elevator intelligent integrated machine EC160 configuration
6
No. Type Function name Function instruction Remarks
inside and outside, go straight to the floor
triggering calling VIP running, and keep
opening. When the elevator responds to
one inside calling after closed manually, it
will exit calling VIP running.
44 Self leveling run
If the elevator is in non-inspection state and
does not stop in the leveling area, the
elevator will return to the leveling and open
the door
Standard
45 UPS running
2 optional running modes: 220V UPS
power switching by F0_22 (need to detect
UPS output feedback and bus fall and set
KPWR logic point into normally closed);
UPS automatic switching (not limited by
UPS voltage and KPWR logic point).
Determine the running direction according
to the load. Power-off input signal is
present in the controller, and when the
power is off, start UPS function
automatically to open the door after low
speed leveling.
Function
selection
46
Automatically return
to the home floor
In non-attendant running mode , automatic
returning signal is valid. If there is no
command, the elevator will return to the
home floor after the delay time. The
elevator can enter standby by F0_18.
Function
selection
47 Lock elevator
In running state, the lock switch acts to
clear all outside calling record. The elevator
runs normally and returns to the home floor
after responding to all recorded commands
in the car. After that, the elevator stops and
turns off the light and fan. The elevator
reruns after lock switch is reset.
Standard
48 Fire evacuation In running state, the fire switch acts to clear Standard