User manual of EC160 elevator intelligent integrated machine Debugging tools
64
Function
code
Name Detailed instruction of parameters
Default
value
F0.18
Relative selection of
elevator running
0~65535
1: Calling below 32 floor connected to inside
line
2: Parallel calling scan in cycle
4: Speed involved in parallel control
calculation
8: Communication IC card enabling
16: No number clearance of internal calling
remote reverse enabling
32: Home floor opening standby enabling
64: During home floor opening standby,
energy saving enabling (Door beam will
automatically cancel energy saving in the
state.)
128: Each floor opening standby enabling
(Energy saving setting will be valid in the
state.)
0
F0.19
Drive CD phase
sampling
0~65535
1: The Max. value in the latest running
2: The Min. value in the latest running
4: The bias out of the latest running calculation
0
F0.20
Filter coefficient of stop
curve
0~65535
Valid range 1~255 (generally unnecessary to
set the value, modifiable when the elevator
shakes after stopping in door area)
0
F0.21
Peristaltic landing
distance
0~65535
Valid range 10~200mm (modifiable when the
asynchronous motor drives by pulley or long
floor rope slides)
0