Goodrive100-PV series solar pumping inverters Function parameters
-26-
Detailed illustration of parameters
Upper limit of the
running frequency
The upper limit of the running frequency is
the upper limit of the output frequency of
the inverter which is lower than or equal to
the maximum frequency.
Setting range: P00.05~P00.03 (Max.
output frequency)
Lower limit of the
running frequency
The lower limit of the running frequency is
that of the output frequency of the inverter.
The inverter runs at the lower limit
frequency if the set frequency is lower
than the lower limit.
Note: Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range: 0.00Hz~P00.04 (Upper
limit of the running frequency)
ACC time means the time needed if the
inverter speeds up from 0Hz to the Max.
output frequency (P00.03).
DEC time means the time needed if the
inverter speeds down from the Max.
Output frequency to 0Hz (P00.03).
GD100-PV series inverters have four
groups of ACC/DEC time which can be
selected by P05. The factory default
ACC/DEC time of the inverter is the first
group.
Setting range of P00.11 and P00.12:
0.0~3600.0s