Goodrive100-PV series solar pumping inverters Function parameters
-49-
Function
code
Name
Detailed illustration of parameters
Default
Modify
P15.13
Empty-water level
threshold
0.0~100.0%
This code is valid when P15.11 water
level control is based on analog input.
If the detected water level control analog
signal is greater than the water level
threshold P15.13 and keeps in the state
after the delay time P15.16, the system
reports A- tL and sleeps. If the delay time
is not reached (that means
non-continuous), the delay time is
automatically cleared. When the
detected water level control analog
signal is less than the water level
threshold, the delay counts.
During the empty-water alarm, if the
detected water level control analog
signal is less than the water level
threshold P15.13 and delay counts, the
empty-water alarm is cleared after the
delay time set by P15.17 in this
continous state. In the non-continuous
state, the delay time is automatically
cleared.
75.0%
P15.14
Full water delay
0~10000s
Time setting of full water delay (This
function code is still valid when the digital
indicates the full-water signal.)
5s
P15.15
Wake-up delay in
full water state
0~10000s
20s