Goodrive100-PV series solar pumping inverters Function parameters
-50-
Detailed illustration of parameters
Time setting of wake-up delay in
full-water state (This function code is still
valid when the digital indicates the
full-water signal.)
0~10000s
Time setting of empty-water delay (This
function code is still valid when the digital
indicates the empty-water signal.)
Wake-up delay in
empty-water state
0~10000s
Time setting of wake-up delay in
empty-water state (This function code is
still valid when the digital indicates the
empty-water signal.)
0.0~100.0%
0.0%: Invalid. If it is not 0.0%, when the
signal is longer than P15.18, it will report
tSF fault directly and stop.
0.0~3600.0s
Delay time of weak light
If the output frequency is less than or
equal to the lower limit of PI output
frequency and the state lasts for the set
value, it will report A-LS and sleep. If the
state is not continuous, the delay
counting will be cleared automatically.
Note: If the bus voltage is lower than the
undervoltage point or the PV voltage is
lower than 70V, it will report the weak