Goodrive100-PV series solar pumping inverters Function parameters
-51-
Function
code
Name
Detailed illustration of parameters
Default
Modify
light alarm without any delay time.
If P15.32=0, the system will switch to the
mains input when the light is weak.
P15.24
Delay time of
wake-up at weak
light
0.0~3600.0s
Delay time of wake-up at weak light
If the weak light alarm is reported, after
the delay time of wake-up, the alarm will
be cleared and it will run again.
When P15.32=0, if the PV voltage is
higher than P15.34, after the delay time,
it will switch to PV input mode.
300.0s
P15.25
Initial reference
voltage display
0.0~2000.0V
0
P15.26
Min. voltage
reference during
max. power
tracking
0.00~1.00
This function code is used to set the
minimum voltage reference during
maximum power tracking. Min. voltage
reference during max. power tracking =
Solar cell panel open-circuit voltage *
P15.26. Solar cell panel open-circuit
voltage = P15.25+ P15.28
Track the maximum power in the range
of Min. voltage reference~P15.27.
P15.27 must be greater than Min.
voltage reference. The less the
difference, the faster the tracking is. The
maximum voltage needs to be in the
range. P15.26 and P15.27 can be
adjusted according to site operation.
0.70