Goodrive100-PV series solar pumping inverters Function parameters
-58-
Detailed illustration of parameters
This function code is set to the bus
reference voltage at PV input when the
system contains the boost module. By
default, this function code is set to 350V
for models of 220V and 570V for models
of 380V.
Setting range: 300.0V~600.0V
If the difference between the bus
reference voltage and actual bus voltage
is greater than 20V, the boost voltage
loop uses this group PI parameter.
Otherwise, the boost voltage loop uses
the first group PI parameter.
Setting range: 0.000~65.535
If the difference between the bus
reference voltage and actual bus voltage
is greater than 20V, the boost voltage
loop uses the PI parameters of this
group. Otherwise, the boost voltage loop
uses the PI parameters of the first group.
Setting range: 0.000~65.535
Once being powered, the boost module
sends its version information to the
converter module.
Note:
The time when the pump inverter operated to the lower limit of PI output frequency after
inverter start-up is determined by the ACC time.