Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-76-
Action selection
at power outage
during
frequency
setting
0x000–0x111
LED ones: Action selection at power outage
during frequency adjusting through digitals.
0: Save the setting at power outage
1: Clear the setting at power outage
LED tens: Action selection at power outage
during frequency adjusting through Modbus
communication
0: Save the setting at power outage
1: Clear the setting at power outage
LED hundreds: Action selection at power outage
during frequency adjusting through other
communication
0: Save the setting at power outage
1: Clear the setting at power outage
MSB of initial
power
consumption
The function codes are used to set the initial
value of the power consumption.
Initial power consumption = (P08.48*1000 +
P08.49)kWh
P08.48 setting range: 0–59999
P08.49 setting range: 0.0–999.9
LSB of initial
power
consumption
Magnetic flux
braking
coefficient
This function code is used to enable magnetic
flux.
0: Invalid
100–150: A greater coefficient indicates greater
braking strength.
The VFD can slow down the motor by increasing
the magnetic flux. The energy generated by the
motor during braking can be transformed into
heat energy by increasing the magnetic flux.
The VFD monitors the state of the motor
continuously even during the magnetic flux
period. So the magnetic flux can be used in the
motor stop, as well as to change the rotation
speed of the motor.
The other advantages include: