INVT iMars MG series grid-tied solar inverters Display panel
Inverter state LED indicators Description
Run
Warn
Fault
(1) Inverter stand-by. Temperature abnormal(E006);
(2) Inverter stand-by. DC input fault (E001);
Yellow indicator keeps on, others off
Unrecoverable
fault
Run
Warn
Fault
Hardware or software fault (E003, E004, E005, E008,
E009, E011, E013 or E015). De-couple the inverter
from the system before maintenance.
Red indicator blinks in every 0.5s, others off
Run
Warn
Fault
Current-leakage or unqualified output power energy of
the inverter (E007, E010, E014, E017, E018 or E020).
De-couple the inverter from the system before
maintenance.
Red indicator keeps on, others off
Artificial
turned off
Run
Warn
Fault
Stop after the communication or panel command. All
indicators are on.
Note
Please refer to chapter 5 and 7 for detailed fault information and troubleshooting.
5.2 Operation panel
There are 4 buttons on the panel:
(1) ESC”, exit and return ;
(2)
”, back to the front page and data increasing;
(3)
to the next page and data decreasing;
(4) “ENT”, enter.
The machine can be turned on and off by pressing the buttons: press "ESC" and "ENT"(about 3
seconds) at the same time, and then the quick start-up and stop is available.