Digital inputs
4 optional digital outputs, semiconductor relays, not short-circuit proof.
Maximum counter frequency 20Hz
Input signal present 18V .. 28V DC (typical 4mA)
Input signal not present 0 .. 5V DC, current less than 0.5A
Cable lengths (digital inputs and outputs)
Up to 30m Unshielded
More than 30m Shielded
Connection capacity of the terminals (digital in-/outputs)
Rigid/flexible 0,14 - 1,5mm
2
, AWG 28-16
Flexible with ferrules without plastic sleeve 0,20 - 1,5mm
2
Flexible with ferrules with plastic sleeve 0,20 - 1,5mm
2
Tightening torque 0,20 - 0,25Nm
Stripping length 7mm
Serial interfaces
RS485 - Modbus RTU/slave 9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps
Stripping length 7mm
USB (receptacle) Type B
Profibus (only UMG96RM-P)
- Profibus DP/V0
- Receptacle
- 9,6kbps to 12Mbps
- D-sub, 9-pole