janitza UMG 96RM-P - Table 2 - Modbus Address List

janitza UMG 96RM-P
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
UMG 96RM-P/-CBM
Table 2 - Modbus address list
(frequently used measured values)
19000 808 float RD V Voltage L1-N
19002 810 float RD V Voltage L2-N
19004 812 float RD V Voltage L3-N
19006 814 float RD V Voltage L1-L2
19008 816 float RD V Voltage L2-L3
19010 818 float RD V Voltage L3-L1
19012 860 float RD A Current, L1
19014 862 float RD A Current, L2
19016 864 float RD A Current, L3
19018 866 float RD A Vector sum; IN=I1+I2+I3
19020 868 float RD W Real power L1
19022 870 float RD W Real power L2
19024 872 float RD W Real power L3
19026 874 float RD W Sum; Psum3=P1+P2+P3
19028 884 float RD VA Apparent power S L1
19030 886 float RD VA Apparent power S L2
Modbus Address
Address Above display Format RD/WR Unit Note
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document “Modbus Address
List” on the CD or Internet.
C
The addresses contained in the descripti-
on can be adjusted directly on the device
in the range from 0 to 800.
The address range 800-999 is available for
programming comparators on the device.
The addresses above 1000 can only be
processed via modbus!