VGD (Enabled/Disabled)
(Software version C.MLM.01.10.xxx (and later) or
C.OPT.01.10.302 (and later))
Access Level Required: SERVICE
Enables and disables the Variable Geometry Diffuser
feature. If equipped with this feature, it should be en-
abled. Otherwise, it should be disabled.
Chiller Style/Compressor
(Flash Memory Card version C.MLM.01.07.xxx and
later)
Access Level Required: SERVICE
Used to enter the chiller style/compressor combination.
Once the applicable chiller style/compressor combina-
tion is entered, the program controls the chiller per the
requirements of the entered chiller style and compressor.
Service Technicians refer to YORK Service Manual
160.54-M1.
Edit Phone Numbers
(Flash Memory Card version C.MLM.01.05.xxx and later)
Access Level Required: SERVICE
Displays up to two service phone numbers. The Regional
service phone number is displayed as the rst number.
Although the label and number can be changed appro-
priately, the default for this entry is “Johnson Controls
North American Toll Free Number 1-800-861-1001”.
The Local service phone number is displayed as the
second number. Although blank by default, the ap-
propriate label and number can be entered by a Service
Technician. Service Technicians refer to Service Manual
160.54-M1.
2
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Setup
Access Level Required: VIEW
Return to the Setup Screen.