REFRIGERANT LEVEL CONTROL SCREEN
LD09099
FIG. 8A
(Software Version C.MLM.01.07.xxx to C.MLM.01.10D.xxx or C.OPT.01.10D (and earlier))
OVERVIEW
This screen displays a cutaway view of the chiller con-
denser, along with the liquid refrigerant level sensor and
variable orice. Some setpoints relating to the liquid
level control are maintained on this screen, while others
are contained on a subscreen. Through animation, the
variable orice position is displayed. In addition, the
refrigerant ow control valve (variable orice) can be
manually operated.
Requires a login access level of SER-
VICE. Service Technicians refer to
YORK Service Manual 160.54-M1 for
operation instructions and explana-
tion of all programmable setpoints and
displayed values.
DISPLAY ONLY
Refrigerant Level Position
Displays the present position of the liquid level. The
refrigerant level is animated in the cutaway view of the
condenser. When the actual level is 0% to 15%, the level
is shown about 50% full. When the actual level is 16%
to 31%, the level is shown about 60% full. When the
actual level is 32% to 47%, the level is shown about 70%
full. When the actual level is 48% to 63%, the level is
shown about 80% full. When the actual level is 64% to
79%, the level is shown as about 90% full. Actual levels
above 79%, shown as 100% full.
Refrigerant Level Control Mode
Indicates whether the liquid level control is under
manual or automatic control.
Raise (LED)
Is ON when the output controlling the Level Raise
contact is on.
Lower (LED)
Is ON when the output controlling the Level Lower
contact is on.
PROGRAMMABLE
Valve Preset Time
Service Technicians refer to YORK Service Manual
160.54-M1.
Ramp-up Time
Service Technicians refer to YORK Service Manual
160.54-M1.