HEAT RECOVERY SCREEN
(Software Version C.OPT.01.21.307)
OVERVIEW
This screen displays all parameters related to the Heat
Recovery feature. It also allows for setting of the
setpoints applicable to this feature.
The Heat Recovery feature is an optional feature and if
so equipped, it must be enabled on the SETUP Screen.
Once enabled, this screen is accessible from the CON-
DENSER Screen. If the Head Pressure Control feature is
also enabled, there is no separate Head Pressure Control
Screen. Rather, the Head Pressure Control parameters
and setpoints appear on this screen. The screen above
is shown with Heat Recovery, Hot Water Control and
Head Pressure Control enabled in ANALOG Control
Source.
When Heat recovery is enabled, the condenser ow
animation will show ow when either the Condenser
Liquid Flow Switch or the Heating Condenser Liquid
Flow Switch says ow is present. When heat recovery
is disabled, the condenser ow animation is based on
the standard Condenser Flow Switch. This screen also
serves as a gateway to controlling the Refrigerant Level,
Heat Recovery and Head Pressure Control.
A complete explanation of the Heat Recovery feature is
contained in Service Manual 160.54-M1.
LD14334
FIG. 7A
OptiView Control Center
Note! – Requires Login access level of SERVICE.
DISPLAY ONLY
Return Heating Condenser Liquid Temperature
Displays the temperature of the liquid as it enters the
heating condenser tube bundle.
Leaving Heating Condenser Liquid Temperature
Displays the temperature of the liquid as it leaves the
heating condenser tube bundle.
Active Hot Water Setpoint
Displays the Hot Water Setpoint to which the Leav-
ing Heating Condenser Liquid Temperature is being
controlled. Only appears when Hot water Control is
enabled.
Return Condenser Liquid Temperature
Displays the temperature of the liquid as it enters the
standard condenser tube bundle.
Leaving Condenser Liquid Temperature
Displays the temperature of the liquid as it leaves the
standard condenser tube bundle.