FORM 160.54-O1
69
JOHNSON CONTROLS
Full Load Amps
Access Level Required: SERVICE
Dene the maximum amps at which the motor can op-
erate. This value is viewable when logged in under the
Operator or View access level. Service Technicians refer
to YORK Service Manual 160.54-M1.
Supply Voltage Range
Access Level Required: SERVICE
Allows the user to select a specic voltage range for volt-
age checking. When not disabled, this line voltage range
is used to determine a low line and high line voltage
threshold for initiating a shutdown. Service Technicians
refer to YORK Service Manual 160.54-M1.
Current Unbalance Check (Enabled / Disabled)
Access Level Required: SERVICE
Allows the user to control whether the logic checks for
current unbalance and initiates a shutdown as a result.
Service Technicians refer to YORK Service Manual
160.54-M1.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Motor Lube
(Software version C.MLM.01.14.xxx (and later) or
C.OPT.01.14.306 (and later))
Access Level required: VIEW
Moves to the subscreen allowing operator acknowledge-
ment of the compressor motor Lubrication and viewing
of the compressor motor lubrication parameters.