K compressor units (metric)
Figure 18: K compressor unit dimensions (mm)
Table 31: Additional operating height clearance
Type of chiller mounting M (mm)
Neoprene pad isolators 44
Spring isolators 25 mm deflection 25
Direct mount 19
Table 32: K1 compressor, evaporator - condenser shell codes
I-K, K–K (mm) M–M (mm) N–N (mm) P–P (mm) Q–Q (mm)
A 2,299 2,616 2,616 2,781 2,781
B 2,921 3,454 3,454 3,493 3,493
C 641 724 724 749 749
D 508 584 584 641 641
E 4,267 4,267 4,877 4,267 4,877
Table 33: K2 compressor, evaporator - condenser shell codes
M–M (mm) M–U (mm) N–N (mm) P–P (mm) Q–Q (mm)
A 2,616 2,896 2,616 2,781 2,781
B 3,454 2,921 3,454 3,480 3,480
C 724 724 724 749 749
D 584 724 584 641 641
E 4,267 4,267 4,877 4,267 4,877
Table 34: K3 compressor, evaporator - condenser shell codes
N–N (mm) Q–Q (mm) R–R (mm)
A 2,616 2,781 2,972
B 3,251 3,505 3,607
C 724 749 813
D 584 641 699
E 4,877 4,877 4,877
Model YK (Style G) Centrifugal Liquid Chiller40

Table of Contents

Other manuals for Johnson Controls YORK YK Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK YK Series and is the answer not in the manual?

Johnson Controls YORK YK Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK YK Series
CategoryChiller
LanguageEnglish

Related product manuals