Functional Desription Operating and Unit Data
Adr.
min max
default
0221h
ru.33 ANOUT1 pre ampl. display
0,1
%
-
400-400
This parameter shows the value of the analog signal ANOUT1 in percent before passing the characteristic amplifier
(also see Chapt. 6.2. ÑAnalog outputsì).
Adr.
min max
default
0222h
ru.34 ANOUT1 post ampl. display
0,1
%
-
115-115
This parameter shows the value of the signal given out on analog output ANOUT1 (terminal X2A.5) in percent. A value
of 0...±115 % correponds to an output signal of 0...±11,5 V (also see Chapt. 6.2 ÑAnalog outputsì).
Adr.
min max
default
0223h
ru.35 ANOUT2 pre ampl. display
0,1
%
-
400-400
This parameter shows the value of the analog signal ANOUT1 in percent before passing the characteristic amplifier
(also see Chapt. 6.2. ÑAnalog outputsì).
Adr.
min max
default
0224h
ru.36 ANOUT2 post ampl. display
0,1
%
-
115-115
This parameter shows the value of the signal given out on analog output ANOUT2 (terminal X2A.6) in percent. A value
of 0...±115 % correponds to an output signal of 0...±11,5 V (also see Chapt. 6.2 ÑAnalog outputsì).
Adr.
min max
default
2025h
ru.37 Motorpoti actual value
0,01
%
-
100-100
The motorpoti-function in the KEB COMBIVERT imitates a mechanical, motor operated potentiometer. The control
occurs via 2 programmable inputs (Ñpoti upì and Ñpoti downì). The display is limited by oP.53/54. The adjustment of the
motorpoti is done with the parameters oP.50...oP.59 (also see Chapt. 6.9.3 ÑMotorpotiì). By way of the bus the motorpoti
can be set to any chosen value between -100...100%. In addition to the inputs the motorpoti can be operated with the
keys ÑUPì and ÑDOWNì. Then the rate of change is not constant.