EasyManua.ls Logo

KEB COMBIVERT G6 - Electrical Operating Conditions

KEB COMBIVERT G6
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.1.4 Electrical operating conditions
3.1.4.1 Deviceclassication
Requirement Standard Class Notes
Overvoltage category
EN 61800-5-1
III
EN 60664-1
Pollution degree EN 60664-1 2
Non-conductive pollution, occasional conden-
sation when PDS is out of service
Table 5: Device classication
3.1.4.2 Electromagnetic compatibility
Fordeviceswithoutaninternallter,anexternallterisrequiredtocomplywiththefol-
lowing limit values.
EMC emitted interference Standard Class Notes
Cable-conducted interferences
EN 61800-3 C2
Radiated interferences EN 61800-3 C2
Interference immunity Standard Level Notes
Static discharges EN 61000-4-2
8 kV
4 kV
AD (air discharge)
CD (contact discharge)
Burst - Ports for process
measurement control lines
and signal interfaces
EN 61000-4-4 2 kV
Burst - Power ports EN 61000-4-4 4 kV
Surge -
Power ports
EN 61000-4-5
1 kV
2 kV
Phase-phase
Phase-ground
Conducted disturbances, in-
duced by radio-frequency
elds
EN 61000-4-6 10 V 0.15...80 MHz
Electromagneticelds EN 61000-4-3
10 V/m
3 V/m
1 V/m
80 MHz...1 GHz
1.4...2 GHz
2...2.7 GHz
Voltageuctuations/
voltage dips
EN 61000-2-1
EN 61000-4-34
-15 %...+10 %
90 %
Frequency changes EN 61000-2-4 ≤2%
Voltage deviations EN 61000-2-4 ±10 %
Voltage unbalance EN 61000-2-4 ≤3%
Table 6: Electromagnetic compatibility