Start-up
© KEB, 2008-02 COMBIVERT R6-S Page 4.2 - 5
4
10
Deactivate regeneration
cS.05 Puls off delay, cS.06 puls off level (CP.32)
If the actual power (ru.81/CP.13)exceedsthedenedvalueincS.06 (CP.32), the modulation is switched off
after expiration of the adjusted time in cS.05.
The settingfortherespectiveapplicationcanbedeterminedasfollows:
- Start-up the drive based on the default values and the adjustment via Pn.19 (CS.33).
- Regenerative operation of the drive, e.g. deceleration process.
- Stop the drive (LS), control release at R6 is active. R6 remains in status ‚rEGEn‘.
- Read actual power ru.81 (CP.13) and enter the value plus one offset of approx.10% in cS.06 (CP.32). R6
changes into status ‚Stb‘
- Check adjustment. R6 must always change into status ,Stb‘ after completion of regenerative operation.
- Increase cS.06 (CP.32) if necessary.