Operating and appliance data
© KEB, 2008-02 COMBIVERT R6-S Page 3.2 - 19
3
10
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
SY.51 Status word low 0033h ro - - 0 65535 1 - 0
The current condition of the COMBIVERT can be readout with the status word. The status word long
(SY.44) consists of the two 16 bit parameters status word high (SY.42) and status word low (SY.51). The
status word is bit-coded.
Bit Value Description
0 1:ST 1=set control release (AND operation with di.1 bit 0)
1 2:Error Inverter is in error state
2
0:Stop The modulation is switched off at „stop“ and switched on at
„start“.
Exception:Ifapositioningisstoppedwithbit11"stop"inthe
control word, "stop" is displayed in the status word, if the drive re-
aches speed 0 (even if modulation is still active). This exception
can be reversed with bit 9 in parameter Pn.65 „special functions“.
4:Start
3
0:Clockwise
rotation
Display of the actual direction of rotation
8:Counter-clockwiserotation
4...6
0:Set0
Display of the actual parameter set.
16:Set1
32:Set2
48:Set3
64:Set4
80:Set5
96:Set6
112:Set7
7
128:Actualvalue=Setpoint
value
ru.07 „actual value display" with a hysteresis of +/- LE.16 „freq./
speed hysteresis“ has the same value as ru.01 „set value dis-
play“
8 256:Faststop Fast stop is active
9 512:HSP5bus-synchronous Inverter in bus-synchronous operation
10
1024:Approachtoreference
point completed
Approach to reference point was executed since the last power
on (or the position was validate otherwise)
11 2048:Positionreached
Display that the positionproleiscompletedandthedriveisin
the range of +/- PS.30 „target window“ near ru.61 „target positi-
on“
12, 13
0:Speedcontrol
Display of the operating mode selected via control word
(only identical with the actual operating mode of the inverter, if in
PS.00 „pos/syn mode“inbits0..2value„7:viacontrolword“is
programmed)
4096:Synchronousrunning
8192:Positioning
12288:Contouringcontrol
14
Posi or approach to reference
point active
Positioning or approach to reference point is active
15 internal limit
The speed setpoint value or any controller (e.g. current,ux,
speed or external PID controller) is in limitation (also in V/f cha-
racteristic open-loop operation)