EasyManuals Logo

Kidde Fire Systems PEGAsys LV User Manual

Default Icon
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
L-2April 2003 76-100016-002
PEGAsys™ LV
The RDCM operator interface needed to enter the pass-
word and access the PEGAsys LV menu is provided via
the alphanumeric keypad:
0–9: Used to enter digits to access PEGAsys LV
menus.
Backspace: Used to exit menu and correct entries.
Enter: Used when selecting from PEGAsys LV
menus.
Note: Operation of above keys will be hereinafter de-
scribed.
The RDCM and RDM operator interface status LEDs for
monitoring the PEGAsys LV and remote modules are:
Alarm: Indicates an alarm condition.
Trouble: Indicates a trouble condition.
Silence: Indicates PEGAsys LV signal/audibles
have been silenced after Acknowledge.
Supervisory: Indicates a supervisory condition.
Power-on: Indicates the system is receiving AC
power.
Pre-alarm: Indicates a smoke or thermal detector
is in pre-alarm condition.
CPU fail: Mounted on main PCB and available to
the installer only. Indicates RDCM/RDM proces-
sor has failed to initialize.
LED colors used to represent indications are:
Red: Alarm.
Green: Power-on.
Yellow: CPU failure, trouble, silence, supervisory
and pre-alarm.
The RDM functions as read only. Therefore, it has a scroll
key, but does not provide the other function keys nor an
operable keypad.
L-2.2 Interconnection
The RDCM and RDM operate on a shared RS-485 bus
which supports wire runs of up to 4000 ft. from the PEGAsys
LV control panel. The primary RS-485 bus from the
PEGAsys LV will support up to fifteen (15) RDCMs and
sixteen (16) RDMs in any combination not exceeding the
maximum for each module.
L-2.3 Addressing
Address selection is via setting of the 16-way, 4-bit hexa-
decimal coded rotary switch, SW1, mounted on the printed
circuit board. See Figure L-4.
Table L-1. Address Switch Settings
hctiwS
gnitteS
MCDR/MDR
sserddA
hctiwS
gnitteS
MCDR/MDR
sserddA
110MCDRroMDR9 90MCDRroMDR
220MCDRroMDRA 01MCDRroMDR
330MCDRroMDRB 11MCDRroMDR
440MCDRroMDRC 21MCDRroMDR
550MCDRroMDRD 31MCDRroMDR
660MCDRroMDRE 41MCDRroMDR
770MCDRroMDRF 51MCDRroMDR
880MCDRroMDR061MDR
L-3 OPERATION
Before proceeding with operations, become totally famil-
iar with PEGAsys LV Fire Alarm Control Unit manual, es-
pecially the sections on Active Alarm Mode, Active
Supervisory Mode and Active Trouble Mode. Be sure to
note differences between latching and non-latching Active
Alarm Modes.
For RX/TX loop input devices: To set either latching or
non-latching, refer to the PCS Operations chapter in the
PEGAsys Configuration Software manual.
Figure L-3. Interconnection of PEGAsys LV Panel, RDM, RDCM(s)
TWISTED UNSHIELDED CABLE
RDCM/RDM
ASSEMBLY
PIN 1 OF TB1 IS AT TOP OF CONNECTOR
NOTE: ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED
POWER SUPPLY
DCM ASSEMBLY
TB1
PINS
AUX.
+
24V
-
5
6
TB1 PINS
IN
1
8
7
2
ASSEMBLY
RDCM/RDM
TIED TOGETHER WHEN
USING THE PANELS
PINS3&4ARE
POWER SUPPLY
TB1 PINS
OUT
65
4
3
IN
7
8
3
REMOTE
DEVICES
UP TO 31
TB1 PINS
6
1
2
4
5
-
+
AUX. SUPPLY
(IF REQ'D.)
24V
TO TROUBLE
CONTACTS
CLOSED = NORMAL
OPERATION
PEGAsys
76-100016-001

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems PEGAsys LV and is the answer not in the manual?

Kidde Fire Systems PEGAsys LV Specifications

General IconGeneral
BrandKidde Fire Systems
ModelPEGAsys LV
CategoryControl Unit
LanguageEnglish

Related product manuals