EasyManua.ls Logo

Klimor HMI Compact - Bacnet MS-TP Communication with the BMS System; Control Via WWW

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79
DEC addres Variable
name
Description / Variables Alarms States
Type Read [R]
/Write
[W]
BacNet Modbus BacNet Modbus
394 788
A_Com
SupFC
Alarm for no communication with the supply inverter 0 - no alarm, 1 - alarm present BV
Coil 12608
R
395 790
A_Com
SupFC2
Alarm for no communication with the supply inverter 2 0 - no alarm, 1 - alarm present BV
Coil 12640
R
396 792
A_Com
ExhFC
Alarm for no communication with the exhaust inverter 0 - no alarm, 1 - alarm present BV
Coil 12672
R
397 794
A_Com
ExhFC2
Alarm for no communication with the exhaust inverter 2 0 - no alarm, 1 - alarm present BV
Coil 12704
R
398 796 A_Tsup Supply temperature sensor alarm 0 - no alarm, 1 - alarm present BV
Coil 12736
R
399 798 A_Texh Exhaust temperature sensor alarm 0 - no alarm, 1 - alarm present BV
Coil 12768
R
400 800
A_Tout
Outdoor temperature sensor alarm 0 - no alarm, 1 - alarm present BV
Coil 12800
R
401 802
A_Trec
Alarm of exhaust temperature sensor behind recovery 0 - no alarm, 1 - alarm present BV
Coil 12832
R
402 804
A_TbackWater
Return water temperature sensor alarm from water heater 0 - no alarm, 1 - alarm present BV
Coil 12864
R
403 806
A_Tmain
Leading temperature sensor alarm 0 - no alarm, 1 - alarm present BV
Coil 12896
R
404 808
A_UV_
LampTime
UV lamp operating time overrun alarm 0 - no alarm, 1 - alarm present BV
Coil 12928
R
405 810 A_InEmul Controller input emulation alarm 0 - no alarm, 1 - alarm present BV
Coil 12960
R
406 812 A_OutForce Controller output forcing alarm 0 - no alarm, 1 - alarm present BV
Coil 12992
R
407 814 Alarm Collective alarm 0 - no alarm, 1 - alarm present BV
Coil 13024
R
5.2 Bacnet MS-TP communication with the BMS system
Search for BacNet variables after connecting the switched
on controller and implementing appropriate BacNet net
-
work settings.
5.3 Control via WWW
The controller can be managed via www protocol.
The shown below optional Ethernet adapter is required as
a hardware element:
Fig. 9 Location for instal ETH module
To connect from a local PC connected directly with ca-
ble with the controller’s ETH adapter:
1. Input the following values in the settings of the PC’s net
-
work adapter for the TCP4 protocol:
Fig. 10 Network module settings of the PC for TCP4 protocol
2. Then open the Internet browser and enter the default
controller address: 192.168.0.8. The window appears
– please enter default login: admin and password: admin
Fig. 11 Login window and access passwords
ETH module with RJ connector

Table of Contents