EasyManuals Logo

Kohler KEP User Manual

Kohler KEP
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
TP-6745 7/10 29Section 2 Troubleshooting
2.8.1 Fault Reset
To clear a fault or warning condition and reset the
System Alert LED, go to the Main screen and press the
down arrow button to open the Reset screen. See
Figure 2-12 and Figure 2-14. Then press the button
labelled Reset. A fault reset does not change the
controller settings.
Fault Message
LD Exer ##/## @ ##:##
Norm ###V Emer ###V
B View Set Test
Reset
Fault Description
BYReset Main
When a fault
message is displayed,
press the down arrow
(B)buttononthe
Main screen to step to
the Reset Fault
screen.
Then press the Reset
button.
Figure 2-14 Fault Reset
2.8.2 Module Status Change
If the Module Status Change message appears on the
controller display, first verify that the cable from the
controller to the accessory module assembly is not
loose or disconnected.
The Module Status Change message automatically
clears if the fault condition is corrected (self-resetting
fault).
Module Connection (new or reconnected module)
Installing or reconnecting one or more accessory
modules triggers the Module Status Change message.
1. If the ATS display shows Module Status Change,
press the Reset button. See Figure 2-15.
Module Status Change
Norm ###V Emer ###V
Reset View Set Test
Reset
New Module
BYReset Main
Press Reset.
Press Reset.
Figure 2-15 Screens after Module Connection
2. The ATS display will show Reset New Module.
Press the Reset button from that screen. The
controller recognizes the module type(s).
3. Navigate to the Set Input/Outputs>Set Aux I/O
screen to check that the controller has recognized
the connected modules. See Figure 2-16.
See the transfer switch operation/installation manual for
instructions to assign programmable inputs and outputs
to I/O modules or assign functions to the audible alarm
for an Alarm Module.
Set Inputs/Outputs
BY"Main
Set
Main Board I/O
BY"Back
Set
Auxiliary I/O
BY"Back
Module 1
Type POB Addr 1
Status: Lost
BY"Back
Module 1
Uninstall Module
Yes
Save Back
Press the down arrow button to step to the
next module, if necessary.
Figure 2-16 Uninstall Module