TP-6714 4/1078 Section 5 Setup
Set Sources, continued
Normal Source
Voltage Unbalance
Dropout
BY"Back
Dropout
??%
5--20%
Save Back
Normal Source
Set Under Frequency
Pickup
BY"Back
Pickup
??? % of Nominal
80--95%
Save Back
Normal Source
Set Under Frequency
Dropout
BY"Back
Dropout
??? % of Pickup
95--99%
Save Back
Normal Source
Set Over Frequency
Pickup
BY"Back
Pickup
??? % of Nominal
105--120%
Save Back
Normal Source
Set Over Frequency
Dropout
BY"Back
Dropout
??? % of Pickup
101--115% Nominal
Save Back
Normal Source
Set Freq Debounce
BY"Back
Debounce Time
?.? Seconds
0.1 -- 15.0 Seconds
Save Back