ELECTRICAL DATA DIRECT DRIVE PSC - 5 TON
Model No. KGB060S4D
1
208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph
Compressor Rated Load Amps 16 7.8 5.7
Locked Rotor Amps 110 52 38.9
Outdoor Fan
Motor
Full Load Amps 1.65 0.8 1
(1) 0.33 HP
Full Load Amps 2.4 1.3 1
Service Outlet 115V GFI (amps) 15 15 20
Motor
0.75 0.75 0.75
Type Direct (PSC) Direct (PSC) Direct (PSC)
Full Load Amps 4.9 2.5 2.5
2
Maximum
Overcurrent
Protection
Unit Only 40 20 15
40 20 15
3
Minimum
Circuit
Ampacity
Unit Only 27 14 10
29 15 12
ELECTRICAL ACCESSORIES
Disconnect Standard Access 20W20 20W20 20W20
Hinged Access 20W26 20W26 20W26
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3