Configuration
Code table
8
8.5
8.5−36
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0582 MONIT OH4 2
2 Warning
Configuration monitoring OH4,
heatsink temperature
l The operating temperature
can be set in C0122
See System
Manual
(extension)
3 Off
C0583 MONIT OH3 3
0 TRIP
Configuration of motor
temperature monitoring with
fixed operating temperature
l Only for KTY at X8
l The operating temperature is
fixed at 150 °C
6.6−11
See System
Manual
(extension)
2 Warning
3 Off
C0584 MONIT OH7 3
2 Warning
Configuration of monitoring
motor temperature with
variable operating temperature
l Only for KTY at X8
l When reaching the
temperature set in C0121 the
warning OH7 is activated
6.6−11
See System
Manual
(extension)
3 Off
C0585 MONIT OH8 3
0 TRIP
Configuration of motor
temperature monitoring
l Temperature monitoring via
PTC input (T1, T2)
6.6−9
See System
Manual
(extension)
2 Warning
3 Off
C0587 MONIT SD3 3
0 TRIP
Configuration of monitoring
SD3, encoder at X9
l Monitors the voltage supply
at X9/pin 8
See System
Manual
(extension)
2 Warning
3 Off
C0588 MONIT
H10/H11
0
0 TRIP
Configuration of monitoring
H10 and H11, thermal sensors in
the controller
l H10: Sensor error − heatsink
temperature
l H11: Sensor error − interior
temperature
See System
Manual
(extension)
3 Off
C0591 MONIT CE1 3
0 TRIP
Configuration of monitoring
CE1, communication error at
CAN−IN1
See System
Manual
(extension)
2 Warning
3 Off
C0592 MONIT CE2 3
0 TRIP
Configuration of monitoring
CE2, communication error at
CAN−IN2
2 Warning
3 Off
C0593 MONIT CE3 3
0 TRIP
Configuration of monitoring
CE3, communication error at
CAN−IN3
2 Warning
3 Off
C0594 MONIT SD6 3
0 TRIP
Activation of the motor
temperature monitoring with
KTY at X8
l Use C0594 = 0 or 2 to
activate monitoring
l In case of a short circuit or
interruption at X8/5 and
X8/8 the fault message SD6
is activated
l Configuration of the
response when exceeding the
motor temperature
Fixed operating
temperature in C0583
Variable operating
temperature in C0584
6.6−11
See System
Manual
(extension)
2 Warning
3 Off