Mains chokes
Mains chokes reduce the
eects of the inverter on the supplying mains.
The switching operaons in the inverter cause high-frequency interferences that will be trans-
mied unltered to the supplying mains. Mains chokes smooth the steep and pulse-like
curves coming from the Inverter and make them more sinusoidal. Moreover, the eecve
mains current is reduced and thus energy is saved.
Mains chokes can be used without restricons in conjuncon with RFI lters.
Please note that the use of a mains choke reduces the mains voltage at the input of the inver-
ter. The typical voltage drop across the mains choke is around 4 % at its rated point.
Inverters from 22 kW must always be used together with mains chokes.
1-phase mains connecon 230/240 V
Inverter Mains choke
Order code Number of phases Rated current Inductance
A mH
i550-C0.25/230-1
ELN1-0900H005
1
5 9
i550-C0.37/230-1
i550-C0.55/230-1
ELN1-0500H009 9 5
i550-C0.75/230-1
i550-C1.1/230-1
ELN1-0250H018 18 2.5i550-C1.5/230-1
i550-C2.2/230-1
1/3-phase mains connecon 230/240 V
Inverter Mains choke
Order code Number of phases Rated current Inductance
A mH
i550-C0.25/230-2
ELN1-0900H005 1 5 9
EZAELN3002B153 3 2 14.7
i550-C0.37/230-2
ELN1-0900H005 1 5 9
EZAELN3004B742 3 4 7.35
i550-C0.55/230-2
ELN1-0500H009 1 9 5
EZAELN3004B742 3 4 7.35
i550-C0.75/230-2
ELN1-0500H009 1 9 5
EZAELN3006B492 3 6 4.9
i550-C1.1/230-2
ELN1-0250H018 1 18 2.5
EZAELN3006B492 3 6 4.9
i550-C1.5/230-2
ELN1-0250H018 1 18 2.5
EZAELN3008B372 3 8 3.68
i550-C2.2/230-2
ELN1-0250H018 1 18 2.5
EZAELN3010B292 3 10 2.94
Accessories
Mains chok
es
1-phase mains connecon 230/240 V