Mains chokes
Mains chokes reduce the
eects of the inverter on the supplying mains.
The switching operaons in the inverter cause high-frequency interferences that will be trans-
mied unltered to the supplying mains. Mains chokes smooth the steep and pulse-like
curves coming from the Inverter and make them more sinusoidal. Moreover, the eecve
mains current is reduced and thus energy is saved.
Mains chokes can be used without restricons in conjuncon with RFI lters.
Please note that the use of a mains choke reduces the mains voltage at the input of the inver-
ter. The typical voltage drop across the mains choke is around 4 % at its rated point.
Inverters from 22 kW must always be used together with mains chokes.
1-phase mains connecon 230/240 V
Inverter Mains choke
Order code Number of phases Rated current Inductance
A mH
i550-C0.25/230-1
ELN1-0900H005
1
5 9
i550-C0.37/230-1
i550-C0.55/230-1
ELN1-0500H009 9 5
i550-C0.75/230-1
i550-C1.1/230-1
ELN1-0250H018 18 2.5i550-C1.5/230-1
i550-C2.2/230-1
1/3-phase mains connecon 230/240 V
Inverter Mains choke
Order code Number of phases Rated current Inductance
A mH
i550-C0.25/230-2
ELN1-0900H005 1 5 9
EZAELN3002B153 3 2 14.7
i550-C0.37/230-2
ELN1-0900H005 1 5 9
EZAELN3004B742 3 4 7.35
i550-C0.55/230-2
ELN1-0500H009 1 9 5
EZAELN3004B742 3 4 7.35
i550-C0.75/230-2
ELN1-0500H009 1 9 5
EZAELN3006B492 3 6 4.9
i550-C1.1/230-2
ELN1-0250H018 1 18 2.5
EZAELN3006B492 3 6 4.9
i550-C1.5/230-2
ELN1-0250H018 1 18 2.5
EZAELN3008B372 3 8 3.68
i550-C2.2/230-2
ELN1-0250H018 1 18 2.5
EZAELN3010B292 3 10 2.94