Fusing and terminal data
Inverter i550-C0.25/230-2 i550-C0.37/230-2 i550-C0.55/230-2 i550-C0.75/230-2
Cable installaon in compliance with EN 60204-1
Laying system B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon ≥ 30 mA, type B
Mains connecon
Connecon X100
Connecon type pluggable screw terminal
Min. cable cross-secon mm² 1
Max. cable cross-secon mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
Motor connecon
Connecon X105
Connecon type pluggable screw terminal
Min. cable cross-secon mm² 1
Max. cable cross-secon mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
Technical data
1/3-phase mains connecon 230/240 V
Fusing and t
erminal data