EasyManua.ls Logo

Lenze i550 - Fusing and Terminal Data

Lenze i550
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fusing and terminal data
Inverter i550-C0.37/400-3 i550-C0.55/400-3 i550-C0.75/400-3 i550-C1.1/400-3
Cable installaon in compliance with EN 60204-1
Laying system B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 10 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 10 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 10 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 10 16
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B
Mains connecon
Connecon X100
Connecon type pluggable screw terminal
Min. cable cross-secon mm² 1
Max. cable cross-secon mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
Motor connecon
Connecon X105
Connecon type pluggable screw terminal
Min. cable cross-secon mm² 1
Max. cable cross-secon mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
Technical data
3-phase mains connecon 400 V
Fusing and t
erminal data
54

Table of Contents

Other manuals for Lenze i550

Related product manuals