Inverter i550-C1.5/400-3 i550-C2.2/400-3 i550-C3.0/400-3 i550-C4.0/400-3
Cable installaon in compliance with EN 60204-1
Laying system B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 16 16 25 25
Circuit breaker
Characteriscs B
Max. rated current A 16 16 25 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 16 16 25 25
Circuit breaker
Characteriscs B
Max. rated current A 16 16 25 25
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Mains connecon
Connecon X100
Connecon type pluggable screw terminal Screw terminal
Min. cable cross-secon mm² 1 1.5
Max. cable cross-secon mm² 2.5 6
Stripping length mm 8 9
Tightening torque Nm 0.5
Required tool 0.5 x 3.0 0.6 x 3.5
Motor connecon
Connecon X105
Connecon type pluggable screw terminal Screw terminal
Min. cable cross-secon mm² 1 1.5
Max. cable cross-secon mm² 2.5 6
Stripping length mm 8 9
Tightening torque Nm 0.5
Required tool 0.5 x 3.0 0.6 x 3.5
Technical data
3-phase mains connecon 400 V
Fusing and t
erminal data
55