EMC-compliant installaon
Structure of a CE-typical drive system
The drive system (frequency inverter and drive) corresponds to 2014/30/EU: EMC Direcve if
it is ins
talled according to the specicaons of the CE-typical drive system.
The structure in the control cabinet must support the EMC-compliant installaon with shiel-
ded cables.
Please use highly conducve shield connecons.
Connect the housing with shielding eect to the grounded mounng plate with a surface as
large as possible, e. g. of inverters and RFI lters.
Use cen
tral earthing points.
Matching accessories makes
eecve shielding easier.
Shield sheets
Shield clips/shield clamps
Metallic cable es
Mains connecon, DC supply
In
verters, mains chokes, or mains lters may only be connected to the mains via unshielded
single c
ores or unshielded cables.
When a line lter is used, shield the cable between mains lter or RFI lter and inverter if its
length exceeds 300 mm. Unshielded cores must be twisted.
In DC-bus operaon or DC supply, use shielded cables.
-
Only certain inverters are provided with this connecon facility.
Voltages for the DC-bus operaon
Voltage on the motor side DC supply Voltage range
V
A
C
V
DC
V
DC
400 565 480 - 0 % ... 622 + 0 %
2/PE
480 675 577 - 0 % ... 747 + 0 %
Project planning
Con
trol cabinet structure
EMC-compliant installaon
20