3-phase mains connecon 230/240 V
Ra
ted data
The output currents apply to these operang condions:
•
A
t a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
•
At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter i550-C4.0/230-3 i550-C5.5/230-3
Rated power kW 4 5.5
Mains voltage range 3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Rated mains current
without mains choke A 20.6 28.8
with mains choke A 15.7 21.9
Apparent output power kVA 6.4 8.7
Output current
2 kHz A 16.5 23
4 kHz A 16.5 23
8 kHz A 16.5 23
16 kHz A 11 15.3
Power loss
4 kHz W 115 175
8 kHz W 130 195
at controller inhibit W 6 6
Overcurrent cycle 180 s
Max. output current A 24.8 34.5
Overload me s 60 60
Recovery me s 120 120
Max. output current during the
r
ecovery me
A
12.4 17.3
Overcurrent cycle 15 s
Max. output current A 33 46
Overload me s 3 3
Recovery me s 12 12
Max. output current during the
recovery me
A
12.4 17.3
Brake chopper
Max. output current A 26 26
Min. brake resistance Ω 15 15
Max. motor cable length shielded
without EMC category m 50
Weight kg 2.1
Technical data