Mains connecon 3-phase, 400 V
Inverter i550-C7.5/400-3 i550-C15/400-3 i550-C30/400-3
i550-C11/400-3 i550-C18.5/400-3 i550-C37/400-3
i550-C22/400-3 i550-C45/400-3
Without RFI lter
Without EMC cat-
eg
ory
Thermal limitaon
Max. motor cable
length shielded
m 100 100 100
Max. motor cable
length unshielded
m 200 200 200
With integrated RFI lter
Category C1 Max. motor cable
length shielded
m - - -
Category C2 m 20 20 20
Earth-leakage circuit
breaker
mA 300 300 300
RFI lter Low Leakage
Category C1 Max. motor cable
length shielded
m - - -
Earth-leakage circuit
breaker
mA - - -
RFI lter Short Distance
Category C1 Max. motor cable
length shielded
m 25 - -
Category C2 m 50 - -
Earth-leakage circuit
breaker
mA 30 - -
RFI lter Long Distance
Category C1 Max. motor cable
leng
th shielded
m 50 50 50
Category C2 m 100 50 50
Earth-leakage circuit
breaker
mA 300 300 300
Low Leakage
Inverter RFI
lters
Order code Rated current
A
i550-C0.25/230-1
I0FAE175B100L0000S 9
i550-C0.37/230-1
i550-C0.55/230-1
i550-C0.75/230-1
i550-C1.1/230-1
I0FAE222B100L0000S 21.8i550-C1.5/230-1
i550-C2.2/230-1
Accessories
RFI
lters / Mains lters
110