Overload capacity of the inverter
£
L,max
M
1.5
M
Braking operaon without addional measures
To decelerate small masses, the "DC
injecon brake DCB" funcon can be parameterised. DC-
injecon braking enables a quick deceleraon of the drive to standsll without the need for
an external brake resistor.
A c
ode can be used to select the braking current.
The maximum braking torque to be realised by the DC braking current amounts to approx.
20 ... 30 % of the rated motor torque. It is lower compared to braking acon in generator
mode with e
xternal brake resistor.
Automac DC-injecon braking (Auto-DCB) improves the starng performance of the motor
when the operaon mode without speed feedback is used.
Braking operaon with external brake resistor
To decelerate greater moments of inera or with a longer operaon in generator mode an
external brake resistor is required. It converts braking energy into heat.
The brake resistor is connected if the DC-bus voltage exceeds the switching threshold. übers-
chreitet. This prevents the controller from seng pulse inhibit through the "Overvoltage" fault
and the drive from coasng. The external brake resistor serves to control the braking process
at any me.
The brake chopper integrated in the controller connects the external brake resistor.
Determine brake resistance
Applicaon
With
acve load With passive load
Rated power P
rated
kW
³ ´h ´ h ´
1
N max e m
z
t
P P
t
´h ´ h
³ ´
max e m
1
N
z
P
t
P
2 t
Thermal capacity C
th
kWs
³ ´h ´ h ´
th max e m 1
C P t
´h ´ h
³ ´
max e m
th 1
P
C t
2
Rated resistance R
r
ated
Ω
Acve load Can start to move independent of the drive (e.g. unwinder)
Passive load Can stop independent of the drive (e.g. horizontal travelling drives, centrifuges, fans)
U
DC
[V] Switching threshold - brake chopper
P
ma
x
[W] Maximum occurring braking power
η
e
Electrical eciency
η
m
Mechanical eciency
t
1
[s] Braking me
t
z
[s] Cycle me = me between two successive braking processes (t
1
+ dead me)
Final conguraon
Product extensions and accessories can be found here:
Pr
oduct extensions ^ 77
Accessories ^ 97
Project planning