Technical data
Communicaon
prole PROFINET RT
Bus terminang resistor not required
integrated bus terminang resistor No
Network topology
Without repeater Tree, star and line
With repeater -
Staon
Type I/O device with real me (RT) communica-
on properes
Max. number 255 Per subnetwork
Address Staon name
Max. cable length m - Not limited
The length between the TNs is decisive.
Max. cable length between two nodes m 100
Process data
Transmit PDOs 16 words
Receive PDOs 16 words
Cycle me ms 2,4,8,16
Switching method Store-and-Forward
Switch latency µs ~ 125 At maximum telegram length
Other data Addional TCP/IP channel
Product extensions
Ne
tworks
PROFINET
95