Multi−axis controllers
Wiring
Devices in the range 47 ... 59 A (22 ... 30 kW)
4
216
EDS94SPP101 EN 10.2
Design of the cables
ƒ The cables used must comply with the approvals required for the location (e.g. UL).
ƒ The cross−section of the PE conductor must be dimensioned according to the
relevant national regulations.
ƒ The effectiveness of a shielded cable is reached by:
Providing a good shield connection through large−surface shield contact.
Using only braided shields with low shield resistance made of tin−plated or
nickel−plated copper braid.
Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ Motor
ƒ Motor holding brake (shielding is required when being integrated into the motor
cable; connection to optional motor brake control)
ƒ Motor temperature monitoring
ƒ Analog signals (inputs and outputs)
ƒ System bus CAN
ƒ Resolver
ƒ Encoder
The following connections need not be shielded:
ƒ 24 V supply
ƒ Digital signals (inputs and outputs)