Single−axis controllers
Rated data
Overview
3
44
EDS94SPP101 EN 10.2
Output data
Voltage Frequency Current [A]
Number of
phases
Type [V] [Hz] up to +45 °C
up to +55 °C
E94ASxE0024 0 − 230/400/480 0 − 599 1.5/1.5/1.3 1.1/1.1/1.0 3
E94ASxE0034 0 − 230/400/480 0 − 599 2.5/2.5/2.2 1.9/1.9/1.7 3
E94ASxE0044 0 − 230/400/480 0 − 599 4.0/4.0/3.5 3.0/3.0/2.6 3
E94ASxE0074 0 − 230/400/480 0 − 599 7.0/7.0/6.1 5.3/5.3/4.6 3
E94ASxE0134 0 − 230/400/480 0 − 599 13.0/13.0/11.4 9.8/9.8/8.6 3
E94ASxE0174 0 − 230/400/480 0 − 599 16.5/16.5/14.4 12.4/12.4/10.8 3
E94ASxE0244 0 − 230/400/480 0 − 599 23.5/23.5/20.6 17.6/17.6/15.5 3
E94ASxE0324 0 − 230/400/480 0 − 599 32.0/32.0/28.0 24.0/24.0/21.0 3
E94ASxE0474 0 − 230/400/480 0 − 599 47.0/47.0/42.0 35.3/35.3/30.8 3
E94ASxE0594 0 − 230/400/480 0 − 599 59.0/59.0/52.0 44.3/44.3/38.7 3
E94ASxE0864 0 − 230/400/480 0 − 599 86.0/86.0/76.0 64.5/64.5/56.4 3
E94ASxE1044 0 − 230/400/480 0 − 599 104/104/92.0 78.0/78.0/68.3 3
E94BSxE1454 0 − 400/480 0 − 599 145/145 131/131 3
E94BSxE1724 0 − 400/480 0 − 599 172/172 155/155 3
E94BSxE2024 0 − 400/480 0 − 599 202/202 182/182 3
E94BSxE2454 0 − 400/480 0 − 599 245/245 221/221 3
E94BSxE2924 0 − 400/480 0 − 599 292/292 263/263 3
E94BSxE3664 0 − 400/480 0 − 599 366/366 329/329 3
E94BSxE4604 0 − 400/480 0 − 599 460/460 414/414 3
Temperature in the control cabinet
Note!
The indicated output voltage will not be reached under certain operating
conditions.
ƒ Output power in the maximum range
ƒ High switching frequencies
ƒ Use of mains filters or mains chokes
ƒ Mains supply with high impedance (U
k
> 5 %)