Rated data
Overview
3
45
EDS94SPP101 EN 10.2
Power losses
Power loss P
V
[W] at a switching frequency of 4 kHz
Type U
Lr
= 230 V U
Lr
= 400 V U
LN
= 480 V when controller is inhibited
E94ASxE0024 70 90 100
40
E94ASxE0034 85 105 120
E94ASxE0044 100 130 145
E94ASxE0074 125 160 180
E94ASxE0134 200 260 290
E94ASxE0174 240 300 340
E94ASxE0244 310 400 450
E94ASxE0324 750 750 750
75
E94ASxE0474 1050 1050 1050
E94ASxE0594 1100 1100 1100
E94ASxE0864 1500 1500 1500
100
E94ASxE1044 1800 1800 1800
E94BSxE1454 2100 2100 < 100
E94BSxE1724 2200 2200
< 100
E94BSxE2024 2600 2600
E94BSxE2454 3300 3300
E94BSxE2924 4100 4100 < 100
E94BSxE3664 4900 4900 < 100
E94BSxE4604 6200 6200 < 150