Single−axis controllers
Rated data
Operation at rated mains voltage 400 V
3
51
EDS94SPP101 EN 10.2
Device size 1 ... 91
Output currents [A] at switching frequency
2 kHz 4 kHz 8 kHz 16 kHz
I
aN2
I
aM2
I
aN4
I
aM4
I
aN8
I
aM8
I
aN16
E94ASxE0024 1.9
3)
6.0 1.9
3)
6.0 1.5 4.8 1.1
E94ASxE0034 3.1
3)
10.0 3.1
3)
10.0 2.5 8.0 1.9
E94ASxE0044 5.0
3)
16.0 5.0
3)
16.0 4.0 12.8 3.0
E94ASxE0074 8.8
3)
21.0 8.8
3)
21.0 7.0 16.8 5.3
E94ASxE0134 16.3
3)
39.0 16.3
3)
39.0 13.0 31.2 9.8
E94ASxE0174 20.6
3)
49.5 20.6
3)
49.5 16.5 39.6 12.4
E94ASxE0244 29.4
3)
58.8 29.4
3)
58.8 23.5 47.0 17.6
E94ASxE0324 38.4 76.8 38.4 76.8 32.0 56.0 16.8
E94ASxE0474 47.0 94.0 47.0 94.0 41.0 82.0 21.5
E94ASxE0594 59.0 118 59.0 118 41.0 82.0 21.5
E94ASxE0864 86.0 172 86.0 172 73.0 146 38.3
E94ASxE1044 104 208 104 208 78.0 156 40.9
E94BSxE1454 145 261 145 261 102 184
E94BSxE1724 172 310 172 310 120 216
E94BSxE2024 202 364 202 364 131 236
E94BSxE2454 245 441 209 376 160 288
E94BSxE2924 292 526 250 450 191 344
E94BSxE3664 366 659 313 563 240 432
E94BSxE4604 460 828 368 662 260 468
I
aN2
Rated value of permanent output current at a frequency of 0 Hz
I
aM2
Maximum output current (overload current) at frequency 0 Hz
E94ASxE0024 ... E94ASxE1044:
Periodic load change of 0.5 s with I
aM2
and recovery time of 4.5 s with
75% I
aN2
E94BSxE1454 ... E94BSxE4604:
Periodic load change of 10 s with I
aM2
and recovery time of 50 s with
75% I
aN2
I
aN4
, I
aN8,
I
aN16
Rated value of continuous output current at a frequency of 5 Hz
(reduce to 0.66 * I
aNx
for 0 ... 5 Hz)
I
aM4
, I
aM8
Maximum output current (overload current) at frequency 5 Hz
(reduce to 0.66 * I
aMx
for 0 ... 5 Hz)
Can be achieved using the setting "x kHz fixed" in C00018
E94ASxE0024 ... E94ASxE1044:
Periodic load change of 0.5 s with I
aMx
and recovery time of 4.5 s with
75% I
aNx
E94BSxE1454 ... E94BSxE4604:
Periodic load change of 10 s with I
aM2
and recovery time of 50 s with
75% I
aN2
bold Nominal value I
aN
3)
Operation with permanent currents > I
aN8
requires an external mains choke.
4)
Depending on the heatsink temperature, the mains voltage and the motor
cable length, the switching frequency can be changed even at smaller currents.