Accessories (overview)
Components for operation in the DC−bus connection
DC−feeding point
8
519
EDS94SPP101 EN 10.2
Safety instructions
Danger!
Hazardous electrical voltage
All power connections carry a hazardous electrical voltage for a longer time
after mains disconnection. Observe the information regarding the discharge
time on the device.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Before working on the power connections, wait at least until the discharge
time has passed (depending on the device, this may be up to 30 minutes).
ƒ Make sure that all power terminals are deenergised.
ƒ Implement active discharge, e.g. by:
– Connection of a discharge resistor when the mains contactor drops.
Safety instructions for the installation according to UL/CSA
Original − English
Warnings!
ƒ Maximum surrounding air temperature: 55 °C
ƒ Use 60/75°C copper wire only, except for control circuits.
ƒ Use appropriate listed (ZMVV) wire connectors and soldering lugs, suitable
for current and voltage.