EasyManua.ls Logo

Lenze L-force 9400

Lenze L-force 9400
646 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single−axis controllers
Rated data
Operation at rated mains voltage 400 V
3
53
EDS94SPP101 EN 10.2
Sinusoidal filter assignments changed for this operating mode:
Max. motor cable lengths for compliance with the conducted interference emission according to C2 when
sinusoidal filters and line filters are used
Type
Setting C01199 Sine filter shielded
unshielded
Switching
frequency
E94BSxE2924 "Mode 1" EZS3−480A200 150 m
− m
2 kHz
or
4 kHz
For the selection "Mode 2:
Output currents [A] at switching frequency
2 kHz
Type I
aN2
I
aNhc
I
aMhc
I
aMre
E94BSxE1454 145 177 195 168
E94BSxE1724 172 212 233 201
E94BSxE2024 202 260 286 247
E94BSxE2454 245 315 347 299
E94BSxE2924 292 395 434 375
E94BSxE3664 366 480 528 456
E94BSxE4604 460 600 660 570
I
aN2
Rated value of continuous output current at a frequency of 0 Hz
(standard operation)
I
aNhc
Increased continuous output current at a frequency of 0 Hz
I
aMhc
Maximum output current (overload current)
Periodic load change of 60 s with I
aMhc
and recovery time of 120 s with I
aMre
I
aMre
Maximum output current during the recovery time
Sinusoidal filter assignments changed for this operating mode:
Max. motor cable lengths for compliance with the conducted interference emission according to C2 when
sinusoidal filters and line filters are used
Type
Setting C01199 Sine filter shielded
unshielded
Switching
frequency
E94BSxE2024
"Mode 2"
EZS3−350A200
150 m
− m
2 kHz
or
4 kHz
E94BSxE2924
EZS3−480A200
E94BSxE4604
EZS3−480A200
(2 in parallel)

Table of Contents

Other manuals for Lenze L-force 9400

Related product manuals