Accessories (overview)
Filters
Mains filters for regenerative power supply modules E94AZMRxxxx (26 ... 47 A)
8
563
EDS94SPP101 EN 10.2
Electrical installation
L3
N
PE
L1
L2
F1...F3
F4
K1
K1
K2
K1
L1 L2
L3
E94ARNE0xx4
X111
-UG
O
I
RFR
+UG
Rb2
Rb1
R
B
R
B
L1 L2
L3
X112
X5
GI
RFR
J
...
+
-
X8
+
+
+
E94AZPP0364
X2
GE24E
+
-
SB
+
-
GE
24E
X323
X324
15
4
4
E94AZMR0xx4xDB
L1 L2
L3
X109
X110
L1.2
L2.2
L3.2
L1.1
L2.1
L3.1
X321
X322
X320
X4
GODO2
K2
"
"
T1
T2
X106
12
3
GN
YE
12
3
GN
YE
94PSPVR01
E94ARNE0xx4 Regenerative power supply module
E94AZPP0364 Installation backplane for the regenerative power supply module
E94AZMR0... Mains filter
F1 ... F4 Fuses
RFR Controller enable (only for regenerative feedback)
K1 Mains contactor
RB Brake resistor ( Mounting instructions brake resistor)
24 V voltage source for the control electronics
(safely separated power supply unit (SELV/PELV) according to IEC 61131−2)
24 V voltage source for the digital inputs according to IEC 61131−2
From FW 02.00: Overtemperature disconnection
DO2 load: max. 50 mA
Mains
Terminal X320 Labelling Description
L1
L2
L3
Connection of the L1, L2, L3 mains phases
Connection for the supply−side PE conductor with M5 ring cable lug
SSP94NF406

Table of Contents