Accessories (overview)
Filters
Mains filters for regenerative power supply modules E94AZMRxxxx (26 ... 47 A)
8
564
EDS94SPP101 EN 10.2
Terminal data
Max. conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
E94AZMR0264xDB 10 6 1.2 ... 1.5 10.6 ... 13.3 1.0 x 4.0
E94AZMR0474xDB 25 2 2.5 22.1 1.0 x 6.5
PE connection data
Æ Starting torque
[mm] [Nm] [lb−in]
E94AZMR0264xDB
M5
3 26.5 PH2
E94AZMR0474xDB
24 V supply
Terminal X323 Labelling Description
GE GND external supply
SSP9400X11
24E 24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131−2, 22.8 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: max. 4 A for 100 ms
Terminal data
Conductor cross−section Tightening torque
[mm
2
] [AWG] [Nm] [lb−in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
Safety instructions for the installation according to UL/CSA
Original − English
Warnings!
Conditions of Acceptability:
ƒ The products are only intended to be used for Lenze Drives E94ARNE0134
and E94ARNE0244.
– All test results are only valid for this Lenze Drives.
ƒ The devices are only evaluated for factory wiring use.